For System Integrators who want a versatile commercial cellular fire alarm communicator, the universal BAT-Fire is equipped with dual Tip & Ring Dial Capture and four programmable inputs/outputs with dual path IP and LTE-M cellular technology, which allows system integrators to save money, maximize install flexibility and skip the 4G cellular sunset.
Near-universal compatibility with FACPs with dialer-capture and point-capture.
Monitor multiple auxiliary building system functions with four programmable inputs and outputs.
Operate at either 12V or 24V and use minimal current to ensure your backup power requirements can be met.
One communicator that works with all panels that use either dialer-capture or point-capture.
Can be configured to comply with any of the most recent UL & NFPA guidelines.
Sole path cellular, IP, or dual-path communications.
Eliminate the inevitable LTE/4G sunset by installing a fire communicator that’s 5G-ready.
Remote programming, troubleshooting and managed over-the-air firmware upgrades.
For System Integrators who want a versatile celular fire alarm communicator, the universal BAT-Fire is equipped with dual Tip & Ring Dial Capture and four programmable inputs/outputs with dual path IP and LTE-M cellular technology, which allows system integrators to save money, maximize install flexibility and skip the 4G cellular sunset.
Housing Dimensions:
8.6 x 5.8 x 2.2 in
Weight:
13.2 oz (372.9 g)
Cover Securing Screw
#6 screw (included)
Mounting Fasteners:
#6 screws and wall anchors (included)
Antenna
External (included)
Reported Indications
Cover Tamper
Inputs
PGM1, PGM2, PGM3, PGM4
Input Ratings
4.7k pullup to 12VDC or 24VDC
Outputs
PGM1, PGM2, PGM3, PGM4, Phone 1, Phone 2
Output Ratings
Open collector outputs, Shunt up to 75mA into ground
BAT-FIRE-VZ
BAT-Fire, Verizon™
BAT-FIRE-ATT
BAT-Fire, AT&T ™
Operating Temperature:
32°F to 120°F (0°C to 48.9°C)
Maximum Humidity
93% non-condensing relative humidity
Power Supply Options
FACP Regulated Supply or UL1481 Listed Power Supply such as Altronix AL300
Current Draw
154mA (Standby) 207mA (Max) @12VDC 109mA (Standby) 161mA (Max) @24VDC
Input Voltage
10V-28VDC
24hr Battery Backup Requirements
12VDC requires 3.7Ahr 24VDC requires 2.62Ahr
Cell
Yes
Ethernet
Yes
WiFi
No
Central Station Receivers
Bosch Conettix: D6600, ITS-D6686-UL, D6100IPv6
Certification Listings:
UL 864 10th Edition, ULC-S559, UL 1610, ULC-S304, CSFM, FDNY
This external power supply is designed to accompany the BAT-Fire FACP communicator. It converts a 115VAC, 60Hz input into a single fused, four, eight or sixteen fuse or PTC protected outputs. Outputs are selectable for 12VDC or 24VDC with a total of 2.5A max.
12VDC or 24VDC selectable output
Indoor/Outdoor Cellular Antenna Kits are designed to increase cellular performance for Connect+™, BAT-Fire™, and BAT-Connect™.